IPN = 500 .. 2000 A
Electrical data
Primary nominal DC & AC current I PN (At rms) 500 800 1000 1500 2000 Primary AC current max. peak value 1) I P (A) 2000 2500 2000 2500 3000 Output voltage (Analog) V OUT (VDC) 0-10 0-10 0-10 0-10 0-10 Type
Features
DC + distorted AC waveform currents measurement True RMS output Busbar or panel mounting Split core type Insulated plastic case recognized according to UL94-V0.
AHR 500 B10 AHR 800 B10 AHR 1000 B10 AHR 1500 B10 AHR 2000 B10
RL VC IC VSL P
Load resistance Supply voltage Current Consumption Output voltage limitation Overload capability (Ampere Turns)
≥ 10 k + 20 .. 50 V DC 35 mA < 14 V 30000 At
Advantages
High isolation between primary and secondary circuits Eliminates insertion loss Easy installation.
Performance data
ε
X
L
VOE TCVOE TCVOUT tr BW
Accuracy @ IPN, TA = 25°C (excluding offset) Linearity error (1% of IPN .. ± IPN) Electrical offset voltage, TA = 25°C Temperature coefficient of VOE ( 0 .. + 60 °C) (- 40 .. + 70 °C) Temperature coefficient of VOUT (% of reading) Response time to 90% of IPN step Frequency bandwidth (±1 dB)
< ±1 % of IPN < ±1.0 % of IPN < ±1.0 % of IPN ± 2.0 mV/K ± 4.0 mV/K ± 0.15 %/K < 150 ms DC, 20 .. 6000Hz